CalcBuiltAll calculators

Wire Size Calculator

Find the wire gauge (AWG) for a circuit from the load in amps, run length, voltage and allowed voltage drop, using NEC ampacity tables for copper and aluminum.

By CalcBuilt Editorial TeamUpdated September 9, 2026Formulas checked against manufacturer specs, see how we calculate.

Quick answer: To size a wire, calculate the circular mils needed to hold voltage drop to 3%, then pick the smallest gauge that meets both that figure and the NEC ampacity for the load. A 20 A load 50 ft from a 120 V panel needs 7,167 circular mils, so 10 AWG copper, which drops 2.07% (2.49 V). This is a planning estimate; a licensed electrician and local code govern.
Your measurements
cut pieceTotal lengthPiece length
A length built from stock pieces: total length divided by piece length, rounded up, with the last piece cut.
Results update as you type. The link in your address bar saves these entries.

Results

Recommended wire size
10 AWG copper
Needs 7,167 circular mils; 10 AWG has 10,380
Voltage drop at that size
2.07%
2.49 V drop, 117.5 V at the load
Minimum size for ampacity alone
12 AWG copper
NEC 75°C column with small-conductor limits, ignoring voltage drop
Continuous load (80% rule)
25 A
If the load runs 3 hours or more, size the breaker and wire for 125% of the load
Planning estimate only
50 ft run
Verify with a licensed electrician; local code, conduit fill, temperature and termination ratings govern

Wire Size formula

Circular mils = 2 x K x Amps x Distance (ft) / (Volts x Drop %)   (K = 12.9 copper, 21.2 aluminum; use 1.732 instead of 2 for three-phase)
Wire size = smallest AWG with circular mils >= required and ampacity >= amps
Voltage drop (V) = 2 x K x Amps x Distance / circular mils of the chosen wire
Continuous load: Amps x 1.25

Worked example

A 30 A, 240 V circuit to a workshop 150 ft away in copper with a 3% limit: 2 x 12.9 x 30 x 150 = 116,100. Divide by 240 x 0.03 = 7.2 to get 16,125 circular mils. 10 AWG (10,380 CM) is too small even though it carries 30 A; 8 AWG at 16,510 CM is the answer. Actual drop: 116,100 / 16,510 = 7.03 V, or 2.9%.

A 50 A, 240 V feeder 100 ft long in aluminum: 2 x 21.2 x 50 x 100 = 212,000, divided by 7.2 = 29,444 circular mils. 4 AWG aluminum (41,740 CM, 65 A) covers both requirements, with a drop of 212,000 / 41,740 = 5.08 V, or 2.1%. 6 AWG aluminum would carry 50 A but drops 8.1 V, or 3.4%.

Quick reference

Maximum one-way run for 3% voltage drop, copper, single-phase
Wire sizeLoad120 V240 V
14 AWG15 A38 ft76 ft
12 AWG20 A46 ft91 ft
10 AWG30 A48 ft97 ft
8 AWG40 A58 ft115 ft
6 AWG50 A73 ft146 ft

How wire size is chosen

Two rules decide the gauge. The first is ampacity: the wire must carry the load without overheating, and the NEC tables give the allowed current for each size. In a house the practical limits are 14 AWG for 15 A, 12 AWG for 20 A, 10 AWG for 30 A, 8 AWG for 40 A and 6 AWG for 50 to 55 A in copper.

The second is voltage drop. Long runs lose voltage in the wire itself, which makes motors run hot and lights dim. The NEC recommends no more than 3 percent on a branch circuit. The calculator finds the circular mils that hold the drop to your limit and then picks the smallest gauge that satisfies both rules. On short runs ampacity wins; past about 50 ft at 120 V, voltage drop usually forces a larger wire.

What this calculator does not cover

This is a planning tool. Ampacities here are the 75°C column with no derating, but bundling more than three conductors in a conduit, ambient temperatures above 86°F, and 60°C terminations on older devices all reduce the allowed current. Aluminum needs compatible lugs and anti-oxidant compound, and is not permitted for most small branch circuits.

Continuous loads such as water heaters, EV chargers and heat pumps must be sized at 125 percent of the nameplate current. Motors have their own rules. Before buying wire or pulling a permit, have a licensed electrician confirm the size against the current NEC and your local amendments.

Key facts

  • The NEC recommends limiting voltage drop to 3% on a branch circuit and 5% on the feeder and branch circuit combined (informational notes to 210.19 and 215.2).
  • K is the resistance of a 1 ft conductor with a cross section of one circular mil: about 12.9 ohms for copper and 21.2 for aluminum at 75°C.
  • NEC 240.4(D) limits 14 AWG copper to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A regardless of table ampacity.
  • Every three AWG steps roughly doubles the conductor area, so 7 AWG has about twice the circular mils of 10 AWG.
  • A load that runs for 3 hours or more is continuous, and the NEC requires conductors and breakers rated for 125% of it.

Frequently asked questions

What size wire do I need for 50 amps?

6 AWG copper or 4 AWG aluminum for ampacity. For runs beyond about 70 ft at 240 V, step up to 4 AWG copper to keep voltage drop under 3%.

What size wire for a 20 amp circuit?

12 AWG copper is the minimum. If the one-way run is longer than about 45 ft at 120 V, use 10 AWG to limit voltage drop.

How far can I run 12 gauge wire on a 20 amp circuit?

About 46 ft one way at 120 V or 91 ft at 240 V before voltage drop exceeds 3% at full load. Lightly loaded circuits can go farther.

Is 3% voltage drop a code requirement?

In the NEC it is a recommendation in an informational note, not a hard rule, but many local codes and energy codes make it mandatory. Follow your local jurisdiction.

Sources and references

Next steps for this project

  1. Electrical Load
  2. Wire Size
  3. Voltage Drop
  4. Conduit Fill
  5. Generator Size
  6. Pipe Size
  7. Water Heater Size

The usual order for a electrical & plumbing project. See all electrical & plumbing calculators.

Results are estimates based on standard formulas and typical product specifications. Confirm quantities with your supplier and local code before ordering.