CalcBuiltAll calculators

Conduit Fill Calculator

Check conduit fill percent for THHN conductors in EMT or PVC with NEC Chapter 9 tables, and find how many wires fit a conduit or the smallest conduit for your wires.

By CalcBuilt Editorial TeamUpdated September 9, 2026Formulas checked against manufacturer specs, see how we calculate.

Quick answer: Conduit fill is the total conductor area divided by the inside area of the conduit, limited to 40% for three or more conductors, 31% for two and 53% for one. Four 12 AWG THHN conductors in 3/4 in EMT use 0.0532 sq in of a 0.533 sq in raceway, a 9.98% fill, and that conduit holds up to 16 of them.
Your measurements
DiameterHeight
A column or tube: volume is the circular area (from the diameter) times the height.
Results update as you type. The link in your address bar saves these entries.

Results

Conduit fill
9.98%
OK: within the 40% limit for three or more conductors (4 x 12 AWG THHN in 3/4 in EMT)
Conductor area used
0.0532 sq in
Allowed 0.213 sq in, which is 40% of the 0.533 sq in inside area
Maximum 12 AWG THHN in 3/4 in EMT
16 conductors
NEC Chapter 9 Note 7: with all conductors the same size, a fraction of 0.8 or more rounds up
Smallest EMT for 4 x 12 AWG THHN
1/2 in EMT
Holds up to 9 of this size
Planning estimate only
NEC Chapter 9 Tables 1, 4 and 5
Assumes all conductors are THHN/THWN of one size. Derate ampacity for more than 3 current-carrying conductors. A licensed electrician and local code govern.

Conduit Fill formula

Conductor area = Number of conductors x Area per conductor (Table 5)   (12 AWG THHN = 0.0133 sq in)
Fill % = Conductor area / Conduit inside area (Table 4) x 100
Limit = 53% for 1 conductor, 31% for 2, 40% for 3 or more (Table 1)
Maximum conductors = Allowed area / Area per conductor, rounded down unless the fraction is 0.8 or more (Note 7)

Worked example

Eight 8 AWG THHN conductors in 3/4 in EMT: 8 x 0.0366 = 0.2928 sq in. The 3/4 in EMT inside area is 0.533 sq in, so the fill is 0.2928 / 0.533 = 54.9%, well over the 40% limit for three or more conductors. Step up to 1 in EMT: the 40% area is 0.346 sq in, and 0.346 / 0.0366 = 9.45, so nine 8 AWG conductors fit and eight of them fill 0.2928 / 0.864 = 33.9%.

Two 4/0 THHN conductors in 1-1/2 in EMT: 2 x 0.3237 = 0.6474 sq in, or 0.6474 / 2.036 = 31.8% of the inside area. The limit for exactly two conductors is 31%, so they do not fit; 2 in EMT at 0.6474 / 3.356 = 19.3% does. Add a third 4/0 and the limit rises to 40%, so three of them (0.9711 sq in, 47.7%) also need 2 in.

Quick reference

Maximum THHN/THWN conductors of one size in EMT (NEC Chapter 9, 40% fill)
EMT size14 AWG12 AWG10 AWG8 AWG
1/2 in12953
3/4 in2216106
1 in3526169
1-1/4 in61452816
1-1/2 in84613822
2 in1381016336

How conduit fill is calculated

The NEC sizes raceways by area. Chapter 9 Table 4 lists the inside area of every conduit type and trade size, along with the area at 40% fill; Table 5 lists the area of each conductor size and insulation type, insulation included. Add up the conductor areas, divide by the inside area of the conduit, and compare with the Table 1 limit: 53% for a single conductor, 31% for two and 40% for three or more. Every wire counts, including the neutral and the equipment grounding conductor.

When all the conductors are the same size, Annex C of the NEC tabulates the answer directly, and this calculator reproduces those numbers for THHN in EMT and Schedule 40 PVC, including the Note 7 rule that lets a result of 0.8 or more round up. Annex C is built on the 40% column even for two conductors; this calculator applies the stricter 31% from Table 1 in that case, which occasionally moves two large conductors up one conduit size.

Beyond the fill percentage

A conduit that is legal at 40% can still be miserable to pull if it has several 90 degree bends, so many electricians plan for 30 to 35% on long runs and keep the total bends between pull points at or under 360 degrees, which is the NEC maximum. Mixed conductor sizes are handled the same way: add the individual Table 5 areas and compare with the 40% area. Other insulation types such as THW or XHHW are thicker than THHN and reduce the count.

Fill is only one limit. Bundling more than three current-carrying conductors in a raceway forces an ampacity derate, and a conduit on a hot roof needs a temperature correction too. PVC also needs expansion fittings on long exposed runs. Have a licensed electrician confirm the raceway, conductor count and ampacity against the NEC edition and amendments adopted where you live.

Key facts

  • NEC Chapter 9 Table 1 limits conduit fill to 53% of the inside area for one conductor, 31% for two and 40% for three or more.
  • The limit for two conductors is stricter than for three because two conductors lie side by side and can jam in the bends; three or more pack more evenly.
  • 12 AWG THHN has an area of 0.0133 sq in including insulation, so 3/4 in EMT (0.533 sq in inside) holds 16 of them and 1/2 in EMT holds 9.
  • Ampacity must be derated when more than three current-carrying conductors share a raceway: 80% for 4 to 6, 70% for 7 to 9, and 50% for 10 to 20 (NEC Table 310.15(C)(1)).
  • Note 4 to Table 1 allows a nipple of 24 in or less between enclosures to be filled to 60%, and the conductors in it are not subject to the bundling derate.

Frequently asked questions

How many 12 AWG THHN wires fit in 3/4 in EMT?

16. The 40% fill area of 3/4 in EMT is 0.213 sq in and each 12 AWG THHN conductor is 0.0133 sq in, so 0.213 / 0.0133 = 16.0. In 3/4 in Schedule 40 PVC the answer is 15.

How many wires can go in 1/2 in conduit?

In 1/2 in EMT, 12 of 14 AWG THHN, 9 of 12 AWG, 5 of 10 AWG or 3 of 8 AWG. Schedule 40 PVC is slightly smaller inside and holds 11, 8, 5 and 3.

Does the ground wire count toward conduit fill?

Yes. Chapter 9 Note 3 says equipment grounding and bonding conductors are included in the fill calculation, using their Table 5 area. They are not counted as current-carrying conductors for ampacity derating.

What is the 40% rule for conduit?

NEC Chapter 9 Table 1 allows the conductors to occupy at most 40% of the conduit's inside area when there are three or more of them. One conductor may fill 53% and two conductors 31%.

Sources and references

Next steps for this project

  1. Electrical Load
  2. Wire Size
  3. Voltage Drop
  4. Conduit Fill
  5. Generator Size
  6. Pipe Size
  7. Water Heater Size

The usual order for a electrical & plumbing project. See all electrical & plumbing calculators.

Results are estimates based on standard formulas and typical product specifications. Confirm quantities with your supplier and local code before ordering.