Conduit Fill Calculator
Check conduit fill percent for THHN conductors in EMT or PVC with NEC Chapter 9 tables, and find how many wires fit a conduit or the smallest conduit for your wires.
By CalcBuilt Editorial TeamUpdated September 9, 2026Formulas checked against manufacturer specs, see how we calculate.
Results
- Conduit fill
- 9.98%
- OK: within the 40% limit for three or more conductors (4 x 12 AWG THHN in 3/4 in EMT)
- Conductor area used
- 0.0532 sq in
- Allowed 0.213 sq in, which is 40% of the 0.533 sq in inside area
- Maximum 12 AWG THHN in 3/4 in EMT
- 16 conductors
- NEC Chapter 9 Note 7: with all conductors the same size, a fraction of 0.8 or more rounds up
- Smallest EMT for 4 x 12 AWG THHN
- 1/2 in EMT
- Holds up to 9 of this size
- Planning estimate only
- NEC Chapter 9 Tables 1, 4 and 5
- Assumes all conductors are THHN/THWN of one size. Derate ampacity for more than 3 current-carrying conductors. A licensed electrician and local code govern.
Conduit Fill formula
Conductor area = Number of conductors x Area per conductor (Table 5) (12 AWG THHN = 0.0133 sq in)
Fill % = Conductor area / Conduit inside area (Table 4) x 100
Limit = 53% for 1 conductor, 31% for 2, 40% for 3 or more (Table 1)
Maximum conductors = Allowed area / Area per conductor, rounded down unless the fraction is 0.8 or more (Note 7)Worked example
Eight 8 AWG THHN conductors in 3/4 in EMT: 8 x 0.0366 = 0.2928 sq in. The 3/4 in EMT inside area is 0.533 sq in, so the fill is 0.2928 / 0.533 = 54.9%, well over the 40% limit for three or more conductors. Step up to 1 in EMT: the 40% area is 0.346 sq in, and 0.346 / 0.0366 = 9.45, so nine 8 AWG conductors fit and eight of them fill 0.2928 / 0.864 = 33.9%.
Two 4/0 THHN conductors in 1-1/2 in EMT: 2 x 0.3237 = 0.6474 sq in, or 0.6474 / 2.036 = 31.8% of the inside area. The limit for exactly two conductors is 31%, so they do not fit; 2 in EMT at 0.6474 / 3.356 = 19.3% does. Add a third 4/0 and the limit rises to 40%, so three of them (0.9711 sq in, 47.7%) also need 2 in.
Quick reference
| EMT size | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
|---|---|---|---|---|
| 1/2 in | 12 | 9 | 5 | 3 |
| 3/4 in | 22 | 16 | 10 | 6 |
| 1 in | 35 | 26 | 16 | 9 |
| 1-1/4 in | 61 | 45 | 28 | 16 |
| 1-1/2 in | 84 | 61 | 38 | 22 |
| 2 in | 138 | 101 | 63 | 36 |
How conduit fill is calculated
The NEC sizes raceways by area. Chapter 9 Table 4 lists the inside area of every conduit type and trade size, along with the area at 40% fill; Table 5 lists the area of each conductor size and insulation type, insulation included. Add up the conductor areas, divide by the inside area of the conduit, and compare with the Table 1 limit: 53% for a single conductor, 31% for two and 40% for three or more. Every wire counts, including the neutral and the equipment grounding conductor.
When all the conductors are the same size, Annex C of the NEC tabulates the answer directly, and this calculator reproduces those numbers for THHN in EMT and Schedule 40 PVC, including the Note 7 rule that lets a result of 0.8 or more round up. Annex C is built on the 40% column even for two conductors; this calculator applies the stricter 31% from Table 1 in that case, which occasionally moves two large conductors up one conduit size.
Beyond the fill percentage
A conduit that is legal at 40% can still be miserable to pull if it has several 90 degree bends, so many electricians plan for 30 to 35% on long runs and keep the total bends between pull points at or under 360 degrees, which is the NEC maximum. Mixed conductor sizes are handled the same way: add the individual Table 5 areas and compare with the 40% area. Other insulation types such as THW or XHHW are thicker than THHN and reduce the count.
Fill is only one limit. Bundling more than three current-carrying conductors in a raceway forces an ampacity derate, and a conduit on a hot roof needs a temperature correction too. PVC also needs expansion fittings on long exposed runs. Have a licensed electrician confirm the raceway, conductor count and ampacity against the NEC edition and amendments adopted where you live.
Key facts
- NEC Chapter 9 Table 1 limits conduit fill to 53% of the inside area for one conductor, 31% for two and 40% for three or more.
- The limit for two conductors is stricter than for three because two conductors lie side by side and can jam in the bends; three or more pack more evenly.
- 12 AWG THHN has an area of 0.0133 sq in including insulation, so 3/4 in EMT (0.533 sq in inside) holds 16 of them and 1/2 in EMT holds 9.
- Ampacity must be derated when more than three current-carrying conductors share a raceway: 80% for 4 to 6, 70% for 7 to 9, and 50% for 10 to 20 (NEC Table 310.15(C)(1)).
- Note 4 to Table 1 allows a nipple of 24 in or less between enclosures to be filled to 60%, and the conductors in it are not subject to the bundling derate.
Frequently asked questions
How many 12 AWG THHN wires fit in 3/4 in EMT?
16. The 40% fill area of 3/4 in EMT is 0.213 sq in and each 12 AWG THHN conductor is 0.0133 sq in, so 0.213 / 0.0133 = 16.0. In 3/4 in Schedule 40 PVC the answer is 15.
How many wires can go in 1/2 in conduit?
In 1/2 in EMT, 12 of 14 AWG THHN, 9 of 12 AWG, 5 of 10 AWG or 3 of 8 AWG. Schedule 40 PVC is slightly smaller inside and holds 11, 8, 5 and 3.
Does the ground wire count toward conduit fill?
Yes. Chapter 9 Note 3 says equipment grounding and bonding conductors are included in the fill calculation, using their Table 5 area. They are not counted as current-carrying conductors for ampacity derating.
What is the 40% rule for conduit?
NEC Chapter 9 Table 1 allows the conductors to occupy at most 40% of the conduit's inside area when there are three or more of them. One conductor may fill 53% and two conductors 31%.
Sources and references
- NFPA 70, National Electrical Code (NFPA)
- Re3 Conduit Fill Calculator (Southwire)
- Code Hunter: Calculations, IAEI Magazine (IAEI)
Next steps for this project
The usual order for a electrical & plumbing project. See all electrical & plumbing calculators.
Results are estimates based on standard formulas and typical product specifications. Confirm quantities with your supplier and local code before ordering.