CalcBuiltAll calculators

AC Size Calculator

Use this AC size calculator to size whole-house central air in tons from conditioned square footage, IECC climate zone, ceiling height, insulation and sun exposure.

By CalcBuilt Editorial TeamUpdated September 9, 2026Formulas checked against manufacturer specs, see how we calculate.

Quick answer: To size central air, multiply the conditioned square footage by 20 to 30 BTU per square foot for your IECC climate zone. Adjust for ceiling height, insulation, sun and internal gains, then divide by 12,000 and round to the nearest half ton. A 2,000 sq ft house in zone 4 with average insulation and 8 ft ceilings comes out at 48,000 BTU per hour, which is 4 tons.
Your measurements
LengthWidthDepth
A rectangular volume: length times width times depth.
Results update as you type. The link in your address bar saves these entries.

Results

Cooling capacity needed
4 tons
For 2,000 sq ft in zone 4, rounded to the nearest half ton because that is how equipment is sold
Cooling load
48,000 BTU per hour
24 BTU per sq ft plus 0 BTU of internal gain
Standard equipment size
4 tons
48,000 BTU per hour nominal. Split systems are sold at 1.5, 2, 2.5, 3, 3.5, 4 and 5 tons, and most lines have no 4.5 ton step
BTU per square foot
24 BTU per sq ft
24 for zone 4, 0% for the envelope, 0% for sun and 0% for ceiling height
Sizing check
Within the rule of thumb
500 sq ft of floor per ton. Manual J on a tight, well shaded house often lands at 700 sq ft to 1,000 sq ft per ton, so treat this as the upper bound
Before you buy
Manual J, then Manual S
Planning estimate only. IRC M1401.3 and IECC R403.7 require the equipment to be picked by Manual S from a Manual J load, and a licensed mechanical contractor pulls the permit

AC Size formula

BTU per sq ft = Zone factor (20 to 30) x envelope factor x sun factor x Ceiling height / 8
Cooling load = Area (sq ft) x BTU per sq ft + 430 x (people - 4) + heat source adder
Tons = Cooling load / 12,000, rounded to the nearest 0.5
Equipment size = nearest of 1.5, 2, 2.5, 3, 3.5, 4 or 5 tons

Worked example

A 1,400 sq ft house on the Gulf Coast in IECC zone 2, with 8 ft ceilings, a tight shell with low-SHGC glass, west-facing and unshaded, five people and an open kitchen. The zone 2 factor is 28 BTU per square foot. Good insulation takes it to 28 x 0.85 = 23.8, and the sun factor takes it to 23.8 x 1.1 = 26.18 BTU per square foot.

The shell load is 1,400 x 26.18 = 36,652 BTU per hour. The fifth person adds 430 and the kitchen adds 1,200, for 38,282 BTU per hour. Divide by 12,000 and you get 3.19 tons, which rounds to 3 tons of standard equipment at 36,000 BTU per hour. That works out to 467 square feet per ton, aggressive even for zone 2, and a Manual J on a house with low-SHGC glass would likely come back at 2.5 tons.

Quick reference

Tons of central air by house area and climate zone (average insulation and sun, 8 ft ceilings, four people)
House areaZone 2, 28 BTU per sq ftZone 4, 24 BTU per sq ftZone 6, 21 BTU per sq ft
1,000 sq ft2.5 tons2 tons2 tons
1,200 sq ft3 tons2.5 tons2 tons
1,500 sq ft3.5 tons3 tons2.5 tons
1,800 sq ft4 tons3.5 tons3 tons
2,000 sq ft4.5 tons4 tons3.5 tons
2,500 sq ft6 tons, two systems5 tons4.5 tons
3,000 sq ft7 tons, two systems6 tons, two systems5.5 tons, two systems

How to size central air in tons

Take the conditioned floor area, multiply by a climate factor, and divide by 12,000. The factor runs about 30 BTU per square foot in zones 1 and 2, 24 in zone 4, and 20 to 21 in the northern zones. It falls going north because the gap between 75 degrees indoors and the design day outdoors shrinks. Scale for ceiling height, since the system cools volume, and adjust 15 percent either way for the shell. Then round to the nearest half ton, because that is the step equipment is built in.

Round to the nearest half rather than always up. A 3.19 ton result belongs on a 3 ton condenser, not a 3.5. Manual S permits a single-speed system to cover 90 to 115 percent of the load, so a unit slightly under the calculated number is normal and correct. Check the answer against square feet per ton as well: this method gives 400 to 600, while a Manual J on a house with a tight shell and good glass often returns 700 to 1,000.

Why oversizing is the classic mistake

An air conditioner does two jobs. It drops the air temperature, which happens fast, and it condenses water out of the air on the cold coil, which happens slowly and only once the coil is fully wet. A unit one size too big hits the setpoint in 5 to 8 minutes and shuts off. The coil never gets wet enough to drain, so the moisture it did collect evaporates back into the house on the next blower cycle. The result is a room at 72 degrees that still feels clammy, which is the complaint that drives people to set the thermostat even lower.

Short cycles cost money in other ways. A compressor draws locked-rotor current on every start, so a system that starts six times an hour instead of twice wears the contactor, the start components and the compressor. Room-to-room temperatures get worse too, because the blower stops before the air in the far bedroom has turned over. If the calculated load lands just above a size, get a Manual J before you order. On a code-built house it almost always comes back smaller than the square-foot rule.

What this calculator leaves out

A square-foot rule cannot see the things that actually set a cooling load. It misses how many square feet of west glass there are and the solar heat gain coefficient on that glass. It also misses ducts running through a 130 degree attic, how leaky the shell is, and how the load splits between floors. A Manual J covers all of that room by room. It also separates sensible from latent load, which is the number that decides whether a house in Houston stays dry. Not included here: the duct design, the return path, the line set and pad, the disconnect and circuit. Nor the condensate drain and secondary pan, the thermostat, permits, or any piping change the move from R-410A to R-454B forces.

Code limits that apply

  • IRC M1401.3checked

    Equipment selected by ACCA Manual S from an ACCA Manual J load calculation

    If you miss it: A permit filed without the load sheet stalls, and the oversized system that gets installed never controls humidity

  • IECC R403.7

    Heating and cooling equipment sized to Manual S using Manual J design loads

    If you miss it: The energy inspection is held until the contractor produces the load calculation for the house as built

  • ACCA Manual S

    Total cooling capacity 90 to 115 percent of the design load in a humid climate

    If you miss it: Capacity above 115 percent leaves the coil dry and the house near 60 percent relative humidity at 72 degrees

  • IRC M1601.1

    Duct systems sized by ACCA Manual D or another approved method

    If you miss it: Old ducts on a bigger system run high static pressure, cut airflow and ice the evaporator coil

  • IRC M1602.2

    Return air taken from inside the conditioned space, not an attic, garage or crawlspace

    If you miss it: A return panned into a closet or garage pulls in dust, fumes and humid attic air the system then has to treat

  • IRC M1305.1.1

    30 in by 30 in of level working space at the service side of the air handler

    If you miss it: An air handler boxed into a closet fails the final and the wall has to be opened back up

Rows marked checked produce a warning in the results when an entry crosses the limit. The others are on the plans or on site and this calculator does not test them. Local amendments can be stricter; the adopted edition and the inspector govern.

Mistakes that cost money

  • Matching the old unit's tonnage. Systems installed before 2000 were routinely a full ton over, so the replacement inherits the mistake.
  • Adding a half ton for an addition that may never be built. That capacity short cycles for the 15 years the system lives.
  • Leaving the ducts alone. A 4 ton system wants about 1,600 CFM, and a single 14 in return trunk cannot carry it.
  • Sizing a two-story house as one zone. The upper floor can be 60 percent of the load while the thermostat sits downstairs.
  • Pairing a new condenser with the old indoor coil. The AHRI certified match sets the rated capacity and the compressor warranty.
  • Chasing humidity with more tonnage in the Southeast. Long runtime is what dries a house out, so the smaller unit wins.

Key facts

  • One ton of cooling is 12,000 BTU per hour, and residential split systems are sold in 1.5, 2, 2.5, 3, 3.5, 4 and 5 ton sizes, with no 4.5 ton step in most lines.
  • ACCA Manual S allows a single-speed air conditioner's total capacity to run from 90 to 115 percent of the Manual J total cooling load in a humid climate.
  • ACCA Manual J counts 230 BTU per hour of sensible heat and 200 BTU per hour of latent heat for each person in the house.
  • IRC M1401.3 and IECC R403.7 both require heating and cooling equipment to be selected by Manual S from an ACCA Manual J load calculation.
  • An oversized air conditioner satisfies the thermostat in 5 to 8 minutes, short of the 10 to 15 minutes of runtime the coil needs to pull real moisture out of the air.

Frequently asked questions

What size AC unit do I need for a 2,000 sq ft house?

About 4 tons by the square-foot rule in a mixed zone 4 climate, which is 48,000 BTU per hour. In zone 2 the same house comes out near 4.5 tons and in zone 6 near 3.5. A Manual J on a code-built house of that size often returns 2.5 to 3 tons instead.

How many square feet does a 3 ton AC cool?

Roughly 1,285 square feet in zone 2 at 28 BTU per square foot, and about 1,715 square feet in zone 6 at 21. Those are rule-of-thumb numbers. A tight house with low-SHGC glass can run 2,000 square feet or more on 3 tons.

Why does my new air conditioner leave the house humid?

Almost always because it is a size too big. It reaches the setpoint before the evaporator coil is wet enough to drain, so it removes very little moisture. A variable speed system, or a correctly sized single-speed unit, runs longer cycles and pulls the humidity down.

Do I need a Manual J to replace my AC?

IRC M1401.3 and IECC R403.7 both require it, and most jurisdictions ask for the load sheet with the mechanical permit. A contractor runs one in about an hour with software, typically $150 to $400 on its own and included with most bids.

Sources and references

Next steps for this project

  1. Insulation
  2. Blown-In Insulation
  3. Attic Ventilation
  4. Heat Loss
  5. BTU
  6. Furnace Size
  7. Mini Split

The usual order for a insulation & hvac project. See all insulation & hvac calculators.

Results are estimates based on standard formulas and typical product specifications. Confirm quantities with your supplier and local code before ordering.